DoldRN5893¶
Handwritten Documentation¶
Electrical safety must be guaranteed during the charging process. For this purpose, an unearthed DC power supply system (IT system) with insulation monitoring is set up and monitored with an insulation monitoring device (IMD). Dold has developed a smart insulation monitoring solution for DC charging stations that also fulfils the requirements of UL 2231. The insulation monitor RN 5893 from the VARIMETER IMD family monitors the charging process from the charging station to the vehicle in combination with the coupling device RP 5898.
Response delay < 10 s
Nominal voltage up to DC 1000 V
Manipulation protection due to sealable transparent cover
Self test¶
The Dold RN5893 supports two types of self tests: the normal self test and the extended self test. This module only supports the “normal” self tests, not the extended self test.
When a self test is started via the IMD interface, bit 4 of the “control word 1” register (address 40001) is set. The device will then perform a self test. If a device fault is present while the self test is running, the self test will fail. If the device reports a state that is not “self test running” anymore and there is no device fault, the self test is considered successful.
Changes of the device state, including self tests, are reported with a short delay via Modbus. This is handled internally using the self_test_running and self_test_triggered variables of the driver.
Timeout¶
The device supports a communication timeout, which raises a device fault if no communication is possible for a certain time.
This module supports this timeout. It is enabled by setting timeout_release to true and optionally configuring the timeout duration in seconds using timeout_s, which defaults to 3s.
This value should not be smaller than 2s, as the driver updates the Timeout register only once per second (or slightly less frequently), which would otherwise lead to false positives.
If the device reports Communication Fault Modbus in the device fault register, the driver will try to reset the device by writing 1 to the control word 1 register. After that, the driver resets the control word 1 to the previous value.
The driver will try to write the device reset command every cycle until the device fault is cleared.
Measurement and publishing modes¶
This driver supports three modes of operation:
Standard mode: The device pauses measurements upon startup and when
stop()is called. Measurements are started by callingstart()Continuous measurement mode: The device continuously performs measurements, bit 8 of the “control word 1” register (address 40001) is not set at any time. This is useful if the device should always alarm on isolation faults, even when no EV is connected. Measurements are still only published when
start()is called, untilstop()is calledThis mode is enabled by setting
keep_measurement_activetotrue
Always publish mode: Like in continous measurement mode, the device continuously performs measurements. Additionally, all measurements are published, even when
stop()is called. This is only useful in very specific scenarios, e.g. if a special module needs measurements all the timeThis mode is enabled by setting both
always_publish_measurementsandkeep_measurement_activetotrue
Device instructions¶
For applications following UL 2231 the parameter
automatic_self_testhas to be disabled (i.e. set tofalse)Changes to modbus registers triggered by modbus messages may have a short delay before they can be read back over the bus. The device’s internal reaction is faster than what is reported via Modbus, however
The device state may not always report “Error” when a device fault is present (i.e. the device has an internal fault or the device fault register reports a fault), because of internal prioritization of faults. Because of this, we only check the device fault register to determine if a fault is present and report that to EVerest
If a modbus communication timeout occurs, the device only responds to modbus requests that either read data or write a reset command