11.2.7. board_support_AC_debug¶
This interface defines the board support debug information that is not used for actual control
11.2.7.1. Variables¶
three_phases:boolean
config option for three phase/single phase operation
three_phases_active:boolean
True if three phases is enabled for current charging session
has_ventilation:boolean
True if ventilated charging is allowed
pwm_running:boolean
True if ventilated charging is allowed
simplified_mode:boolean
True if car uses simplified mode of IEC61851
rcd_reclosing_allowed:boolean
True if RCD may reclose after fault according to local regulations
is_power_on:boolean
True if Relais are currently closed (power on)
cp_hi_voltage:number
Voltage of high part of PWM
cp_lo_voltage:number
Voltage of low part of PWM
supply_12V_voltage:number
Voltage of +12V supply
supply_N12V_voltage:number
Voltage of -12V supply
rcd_current:number
Residual current measurement