13.1.28. PowermeterBSM¶
Module that collects power and energy measurements from a MODBUS RTU device
13.1.28.1. Module Configuration¶
power_unit_id:integer <required>
Modbus unit_id, mostly 1
sunspec_base_address:integer <optional>
default: 40000
sunspec base address of device ( 0, 40000 or 50000 )
update_interval:integer <required>
Update interval in seconds.
watchdog_wakeup_interval:integer <optional>
default: 60
wakup interval of watchdog in seconds (default 60 seconds).
serial_device:string <optional>
default: “/dev/ttyUSB0”
Serial port the BSM hardware is connected to
baud:integer <optional>
default: 19200
Baud rate on RS-485, allowed value range: 2400 115200 (19200 is default)
use_serial_comm_hub:boolean <optional>
default: True
When enabled, use a serial serial_communication_hub, otherwise use the configured serial device.
meter_id:string <optional>
default: “no_meter_id”
Arbitrary string id, used as power_meter_id in interface powermeter.
13.1.28.2. Provides¶
13.1.28.3. Requirements¶
serial_com_0_connection:serial_communication_hub 0..1