10.12. sunspec_ac_meter¶
sunspec ac powermeter types
Result:object
Measured dataset
required: timestamp
properties:
timestamp:integer
Timestamp of measurement
ID:integer
ID Model ID uinteger no 203 SunSpec Model AC Meter
L:integer
L Model Payload Length uinteger no 105 Without the fields ‘Model ID’ and ‘Length of payload.
A:integer
A Amps int16 A no
AphA:integer
AphA Amps PhaseA int16 A no
AphB:integer
AphB Amps PhaseB int16 A no
AphC:integer
AphC Amps PhaseC int16 A no
A_SF:integer
A_SF integer no
PhVphA:integer
PhVphA Phase Voltage AN int16 V no
PhVphB:integer
PhVphB Phase Voltage BN int16 V no
PhVphC:integer
PhVphC Phase Voltage CN int16 V no
V_SF:integer
V_SF sunssf no
Hz:integer
Hz Hz int16 Hz no
Hz_SF:integer
Hz_SF sunssf no
W:integer
W Watts int16 W no
WphA:integer
WphA Watts phase A int16 W no
WphB:integer
WphB Watts phase B int16 W no
WphC:integer
WphC Watts phase C int16 W no
W_SF:integer
W_SF sunssf no
VA:integer
VA VA int16 VA no
VAphA:integer
VAphA VA phase A int16 VA no
VAphB:integer
VAphB VA phase B int16 VA no
VAphC:integer
VAphC VA phase C int16 VA no
VA_SF:integer
VA_SF integer no
VAR:integer
VAR VAR int16 var no
VARphA:integer
VARphA VAR phase A int16 var no
VARphB:integer
VARphB VAR phase B int16 var no
VARphC:integer
VARphC VAR phase C int16 var no
VAR_SF:integer
VAR_SF sunssf no
PFphA:integer
PFphA PF phase A int16 Pct no
PFphB:integer
PFphB PF phase B int16 Pct no
PFphC:integer
PFphC PF phase C int16 Pct no
PF_SF:integer
PF_SF sunssf no
TotWhIm:integer
TotWhIm p Total Watt-hours Imported acc32 Wh no
TotWh_SF:integer
TotWh_SF sunssf no
Evt:integer
Evt Events bitfield32 no See chapter 17.5 Event flags of critical events of counter and communication module. A problem exists if this value is different from zero.